TransWikia.com

Wire size for emergency generator and 200 amp ats switch

Home Improvement Asked by Stuart Onsrud on June 29, 2021

I have approximately 85 ft run between emergency generator and ats switch. 5 ft buried, then up exterior wall then through attic then down exterior wall to ats panel. I intend to use #1 awg 3 conductor SER with ground but not sure of the rated heat and if #1awg is correct.

One Answer

200 amps will require 3/0 copper or 4/0 aluminum we would need to know how heavily loaded the circuit is expected to provide the correct wire size & for voltage drop.calculator This is easy to use code requires less than 3%. Put in your voltage 85' and expected full load.

Answered by Ed Beal on June 29, 2021

Add your own answers!

Ask a Question

Get help from others!

© 2024 TransWikia.com. All rights reserved. Sites we Love: PCI Database, UKBizDB, Menu Kuliner, Sharing RPP