Home Improvement Asked by natsuki_2002 on December 18, 2020
I’m going to list the 3 scenarios for electrocution I can think up for both a residential transformer with grounded neutral and an isolated transformer. I find that the grounded neutral transformer has one more scenario in which I get electrocuted than the isolated transformer does and I want to know why despite this, we reference neutral to ground in residential systems. I have heard it is for safety reasons but my thinking suggests that it is actually more dangerous to reference neutral to ground. I’m hoping someone can clear this up for me.
Imagine I’m standing at my main breaker looking at my hot and neutral lugs. For all of the examples below please imagine I’m not standing on any insulated platform. I’m barefoot on some kind of wet concrete floor. I’m also explicitly talking about the service entrance wires to do away with any complications coming from different branch circuits inside the home. Please assume I’m just talking about the service entrance wires.
I’m also going to talk about the current as if it were DC current and electrons come from the hot lug towards neutral. This is just because it helps get my ideas across in English easier. But please understand that I do realize that current will be flowing in both directions on an AC circuit.
Regular Residential Transformer w/ Grounded Neutral
Isolated transformer (Neutral not grounded)
Now imagine that my residential transformer was not referenced to ground at the neutral point. Imagine it is like an isolated transformer.
I touch the hot lug. There is a (very likely – but unknown) potential difference between the concrete floor and the hot lug. However, there is no unlimited source of electrons like a grounded neutral. There is a limited source of electrons which is the wires inside the transformer themselves. I may get a small shock similar to static electricity shock as my body and concrete floor get brought up to the same potential as the hot lug but ultimately there can be no flow of electrons because there is no sustainable source for them to come from. They will push into my body because of the potential difference but at some point the transformer conductors will be so electron deficient that the force on the electrons to stay will be greater than the force they feel to push into my body.
I touch the neutral lug. It is unlikely that there is a potential difference between the neutral lug and the wet concrete floor so I will very likely feel no static-electricity like shock. In addition for the same reasons as above, even if there is a potential difference between the neutral lug and ground there is no sustainable source for electrons to come from so again I do not get electrocuted.
I touch both the hot and neutral lugs at the same time. Current flows through my body and I get electrocuted.
Electrocution Breakdown
So given this breakdown why do we ground neutral? Seems like it only introduces scenarios to get electrocuted. We could even have ground faults with an isolated transformer and not get electrocuted. Seems more dangerous to ground than to not.
I know you're looking for a "tweet" of an answer, a simplistic reason "Oh, it's this". There's actually a lot to it. It's not an ideology, it's hard empirical data culled from a sea of accident reports. They are using field data to "min-max" for minimum casualties.
That is a thing. And yes, if properly maintained, it amounts to "your first ground-fault is free".
I discuss the matter at length in this posting.
However, that "first ground fault" creates a treacherous situation for the rest of the system.
I had exactly that happen on a system I did not intend to be isolated. I found it when working on a circuit that I had turned off, and I flashed hot to ground just to be sure of it, and I got a tiny blue arc, and the fluorescent lights on that circuit came back on. The neutral was 120V from ground (whoopsie!) and the other phase was 240V from ground. Neutral was now dangerous, even though I had turned off the breaker, and it was a darned good thing I had done the "flash test" and chased down the problem before proceeding, because I was about to handle neutral in a grounded metal box, and that would've kicked my butt.
So "the first ground fault is free" is only clever if you have maintenance people actively searching and testing for that first ground fault, and they repair it BEFORE a second ground-fault occurs. Otherwise, it simply fails in silence, creating a time-bomb that is a worse situation than a grounded system, and bites you later with very unexpected behavior.
Indeed, Code does allow isolated systems on sites where on-site staff do active maintenance and monitoring of the system. That's sure as heck not a house.
Correct answer by Harper - Reinstate Monica on December 18, 2020
Neutral is grounded in power distribution systems because power lines are on the top of poles and are enticing places for lightning strikes. It is not grounded to enhance electrocution safety for people who want to install electrical outlets in their shower stalls to power their radios while they take a shower...LOL
By grounding neutral they can install spark gaps in the distribution network to allow lightening to be bled off to ground instead of coming into people homes over the downlead and exploding their TV sets off the wall.....
If you had an entirely underground distribution system you could forgo the ground on the last stepdown into the customer premise and probably make it safer.
I hope you get an A on your essay... ;-)
Answered by Ted Mittelstaedt on December 18, 2020
Get help from others!
Recent Questions
Recent Answers
© 2024 TransWikia.com. All rights reserved. Sites we Love: PCI Database, UKBizDB, Menu Kuliner, Sharing RPP