TransWikia.com

What would cause my line sets to equalize in cooling mode?

Home Improvement Asked by Roger Kincaid on September 27, 2021

My heat pump line sets only get different temperatures briefly on startup in cooling mode. Then the hissing noise stops and they equalize and only the lower 1/4th of the a-coil gets cold and condensates. In heat mode they seem to work fine, one hot and one cold. A tech came out and said i was low on refrigerant 410a and added it to my system. I still have the same problem.

I have a Nordyne split system electric heat pump. Model #JT4BD-030K 2.5 Ton Phase 1

One Answer

Try to find a good heat pump guy and not the "fool" you called before. The problem could be a faulty reversing valve, faulty compressor, refrigerant charge, bad metering valve or piston or any number of other conditions. Most guys just attach hoses and add more refrigerant without looking for the REAL problem. They know very little of what happens or is supposed to happen at any point in the refrigeration cycle. Many of the problems associated with an A/C unit or heat pump can be diagnosed without the use of a set of gauges and a bottle of refrigerant. A real service tech will stop, listen and touch before getting the tool box. This reminds me of a real life story that I observed many years ago. The tech replaced the compressor, contactor, high and low pressure controls, thermostat and control transformer, each on different calls only to find out that the real problem was a burned out control fuse. True story. And this guy had years of experience. my 2 cents

Answered by d.george on September 27, 2021

Add your own answers!

Ask a Question

Get help from others!

© 2024 TransWikia.com. All rights reserved. Sites we Love: PCI Database, UKBizDB, Menu Kuliner, Sharing RPP