Home Improvement Asked on December 10, 2020
I am running 4 new circuits. 6/3 (50A 240V) Romex, 8/3 (40A 240V) Romex, as well as a couple of 12/2s.
Cables start at the far end of the boiler room from a panel, through 1.5" holes of several exposed joists, followed by finished basement (quite wide 3-4 ft) soffit that currently houses lots of other cables and wires, followed by stud space to the upper-level kitchen.
Is this to the code? Is it okay to run 6/3, 8/3, and two 12/2s in a single joist hole bunched together? Is it then okay to just have those wires laying in the soffit, since they are fished through? Just before they leave the basement for the stud space above, they are in close proximity with PEX tubing so want to double-check that as well. And once inside the stud space (they will branch out through holes to the other studs to the final outlet locations), do I need to put some kind of protective plating or conduits or would stapling them to the middle of 2×4 studs suffice?
In my jurisdiction they would call that bundling and flag it. They normally won’t say anything with 2 cables and some areas up to 4 but when there are more than 3 current carrying we have to start derating
over 8 current carrying conductors the built in safety in #14, #12 
 exceed what is allowed.
there can be some issues there even though nipples less than 24” don’t have to be derated a long run like in the photo is normally flagged with more than 4 is all the states I have worked in.
I see 6-3 , 8-3 & 12-2 x2 10 current carrying conductors as I said most jurisdictions would flag this as bundling.
Correct answer by Ed Beal on December 10, 2020
Get help from others!
Recent Questions
Recent Answers
© 2024 TransWikia.com. All rights reserved. Sites we Love: PCI Database, UKBizDB, Menu Kuliner, Sharing RPP