Home Improvement Asked by ATS on September 29, 2021
Currently I have dual transformer system
From heat >> RH & W1
From cool >> Y1, Rc, G
Honeywell provides a C wire adapter and also mentioned turning an unused wire into a C-wire. I do have an unused wire from the cool side. Mentioned in the manual is all about joining the adapter OR if there is an extra wire to furnace. My furnace wire up to the thermostat is only 2 wires.
Is it possible to use the cool transformer for the extra wire? Since I do have 2 unused wires
Thanks!
From the pictures given, it does appear that the blue wire from the air handler is connected to C, so I'd just use that as your C wire. Let us know how it goes!
Correct answer by ThreePhaseEel on September 29, 2021
Get help from others!