Ecobee 3 lite Installation -- Confusion about C wire (on furnace but not at thermostat)

Home Improvement Asked on September 6, 2020

I am about to install the Ecobee 3 lite thermostat. On the thermostat end, there is no C wire – just the typical 4 wires – R,Y,W,…

On the furnace end though, there is white C wire too, which I do not know where it leads to (definitely not coming to thermostat).

Given the situation, following are questions I am looking answers for:

  1. Can I simply remove the existing C wire and replace with the C wire from the PEK kit from Ecobee? Wondering what else may break in the house.
  2. Can I simply keep the existing C wire as is, and add the C wire from the PEK kit in addition, at the same terminal?

Any info or any tips that can help me out in this situation are highly welcome.

enter image description here
enter image description here
enter image description here
enter image description here
enter image description here

One Answer

You can connect two wires to this terminal

You can indeed connect the C wire from the PEK to this terminal in addition to the air conditioner's C wire. If you look closely at your Y terminal, in fact, you will see it is already double-tapped with the Y wire from your thermostat and the Y wire to your air conditioner.

Answered by ThreePhaseEel on September 6, 2020