TransWikia.com

double pole breaker trips all the time

Home Improvement Asked by Dude from SF on June 9, 2021

enter image description here

First of all, I have a dumb question: does this white double pole breaker offer 20A or 40A (20A+20A as labeled) in total?

This double pole breaker controls both pool pump and washer (washing machine).

It trips all the time, and one time, the outlet for the washer was even burned out. Sometimes pool pump would suddenly stopped and lost power.

For the pool pump, it uses 10 Amps max, and for the washer, it uses 20 Amps max. Also, the pool pump was recently replaced and has some air inside sometimes.

Anyone know what might be the issue here?

3 Answers

Could be an overload

This is a 240V (2-pole) breaker. Given the 20A size, it is perfectly legal for it to feed both 120V and 240V loads, and I suspect the pool pump is a 240V load.

A 20A 240V/2-pole breaker has two poles (legs) of 20A each.

A 120V load can draw off one leg and neutral, and it will draw the amps it says.

A 240V load will draw off both legs at once and will draw the amps it says.

So for instance, your pool pump draws 10A from L1 and 10A from L2.

Your washer draws 20A from L1. Let's add em p.

  • L1: 10A pool pump. 20A washer. Total 30A
  • L2: 10A pool pump. Total 10A.

30A is more than 20A. Whoops!

Or, it could be a ground fault problem

That particular breaker is a GFCI (Ground Fault Circuit Interruptor) breaker. It is looking out for ground faults, which is leakage from the places power is supposed to be, to places power is not supposed to be.

Such leakage is exceedingly common with electrical machines that handle water.

It can also happen in wiring, particularly outdoor wiring.

If you are getting trips when the washing machine is not running, this is likely the problem.

You would need to eliminate one appliance at a time by unhooking all of its wires (hot(s) AND neutral) from the system. You must unhook neutral or the test will be invalid. You don't need to unhook safety ground. If you unhook an appliance and the problem goes away, that appliance is faulty.

Correct answer by Harper - Reinstate Monica on June 9, 2021

"I have a question: does this white double pole breaker offer 20A or 40A (20A+20A as labeled) in total?"

20A - At 240V.

If your washer draws 20A and your pool pump draws 10A, hardly surprising it would blow, since that would be 30A draw. So it would be reasonable to expect it to blow any time both are on at once, or at least any point in the wash cycle where your washer is drawing full load and the pool pump is on.

This is also a moderately blatant code issue, since the power for the washer and dryer is not supposed to share with any other room/function.

Answered by Ecnerwal on June 9, 2021

First that is a 20 amp circuit it could be 240v but sounds like 2 each 20 amp 120v circuits that are both protected by a 20 amp breaker (not the same as 40 amp).

That is a GFCI breaker (I can just barely read ground fault on the tag) . Having multiple loads like the washer and pool pump suggest it is a multiwire branch circuit.

Multi-wire branch circuits have become less popular because because of GFCI requirements and false tripping.

The receptacle that failed probably back stabs were used (although 20 amp should not have back stabs I have found this and loose connections to melt a device). because of the small contact area the connection was not a good one that overheated to the point of melting down. But either circuit drawing +20 amps will cause this to trip.

Or a ground fault with a 5ma value can cause this to trip.

1 problem with GFCI’s on motor circuits is they measure the current on the line and the neutral if there is an imbalance of greater than 5ma or 0.005 amps they trip.

Motors create an imbalance in the voltage and current and by themselves and can sometimes cause false trips by themselves, but having motor loads on both sides can make the problem worse.

Today’s code requires the washing machine to be on its own circuit, I have had problems with gfci’s and my state allows me to change that dedicated circuit to a standard breaker. I would check your state rules and if the washer is close to the panel I might convert to separate circuits. The pool will still need GFCI protection but being on a separate single pole breaker with a weather resistant GFCI outside where it can be reset is what I would do and there will be less tripping.

If your state still requires a GFCI device and you don’t want to replace wiring. I have found in this type of case a separate GFCI device in each place(1 at washer and 1 for the pool) with and a standard double pole breaker to have less trips, however having a common neutral they still may trip.

Answered by Ed Beal on June 9, 2021

Add your own answers!

Ask a Question

Get help from others!

© 2024 TransWikia.com. All rights reserved. Sites we Love: PCI Database, UKBizDB, Menu Kuliner, Sharing RPP