TransWikia.com

AC Blower Motor not working during night

Home Improvement Asked by Blazing Saddles on February 20, 2021

The blower motor in the furnace stops working at night most of the time when the AC should be on. The blower motor (in the furnace) might run for one or two cycles at the beginning of the night but then it stops working the rest of the night. The outside condenser will run all night, draining my bank account, since it’s being told to by the thermostat. Because the blower motor stays off most of the night, this causes the AC lines to freeze from the compressor (outside) to the evaporator (inside on furnace). At some point during the morning, the blower motor starts working again somewhere around the time where the thermostat set point changes (programmable thermostat) and everything thaws out and starts working again. During the daytime, there seems to rarely be problems, but they do happen occasionally as verified by my online data gathered by the smart thermostat (Ecobee).

I have tested as follows. At 2:00AM, when AC lines are frozen, the condenser is running (fan and compressor), and the blower motor is called for but not working, I completely shut off the system at the thermostat. I then use the thermostat’s installation testing feature to manually turn on the “fan” (aka blower motor). The blower motor does not come on even though I have verified 28VAC is present at the “G” (fan) connection at the furnace when this manual test is activated. I have even disconnected power completely to the furnace, waited 10 minutes, plugged everything back in, and still see the same results most of the time.

When the problem persists for 4 or more hours, the thermostat will detect something is up and display the following on the screen – “Cooling problem… There may be a problem with the Cooling system. For the past 4 hours the thermostat has been calling for cool, but the room temperature has increased by 3.9F”

My AC repairman has taken out the blower motor and tested everything, seeing no issues. Now a new motor control board is on the way but I’m a bit skeptical that this will solve anything after reading some other posts on Stack Exchange with similar issues and no solutions…

Update: The new motor control board was installed yesterday and everything worked during the day. However, the system again froze last night after the furnace blower motor had been non-functional for enough time. The thermostat again displayed the “Cooling problem…” alert as we were sweating in bed. The low pressure line outside was a Popsicle when I checked it at sunrise as the system continued to cycle on/off with no blower motor.

2 Answers

You may have a run capacitor for the blower fan that is going bad.

Answered by CoreyF on February 20, 2021

Do you have an electric water heater on a timer that turns off the heater elements at night? I can imagine a weird and unsafe cross-connection between the air handler and the water heater. Perhaps the power line to the A/C lacks a neutral wire or some such because a previous A/C system didn't need one, but your newer one does.

To test the theory, pick a time when the A/C is running correctly and blowing cold air, then turn off the water heater's breaker at your electric panel. If the A/C blower stops, you found your problem.

Answered by MTA on February 20, 2021

Add your own answers!

Ask a Question

Get help from others!

© 2024 TransWikia.com. All rights reserved. Sites we Love: PCI Database, UKBizDB, Menu Kuliner, Sharing RPP